Understanding the basics of power measurement theory

- Advertisment -

Electrical power applications are changing rapidly. LED lighting is replacing incandescent lamps, variable speed motor drives replace directly coupled electric motors, and photovoltaic (PV) installations and wind turbines generate additional electrical power. This means the load on the electric network is changing. More harmonics and more risk of unbalance.

This so called “bad” power costs money and wastes energy. This article provides some basic theory to understand what is happening with today’s electrical applications.

Apparent power

To understand the relation between active power P, reactive power Q and apparent power S, consider the historical “canal boat” metaphor in Fig. 1. The boat stands for the electrical load, the horse for the generator and the cable from the horse to the mast for the electrical network. Because the horse is not pulling exactly in front of the boat but at an angle, it has to deal with two forces: the desired forward pointing force P and the unwanted sideward force Q.

Fig. 1: The “canal boat” metaphor for understanding the relationship between active, reactive and apparent power.

The strain on the cable is, according Pythagoras, the square root of the sum of P squared and Q squared. In a similar way the electrical network has to deal with two powers if the voltage and current of a load are at an angle to each other: The active power P, doing the work, and the reactive power Q, wasting network resources. To complicate matters, harmonic components SN on the network, symbolised by choppy waves beneath the boat, stress the cable between horse and boat, and hence the electrical network, even further. The horse gets tired faster and we pay money for wasted electrical energy.

Harmonics

To be able to do something about this waste of money and energy we first must be able to distinguish between phase shift and harmonics. These disturbing phenomena each require different counter measures. With Fourier analysis we can separate fundamental and harmonic power. The fundamental power can be split into an active part pa(t) and a reactive part pr(t). What is left after the fundamental power is split off, is the harmonic power pH(t).

Fig. 2: Phase shift and harmonics.

The active part does the real work: It transfers useful energy from the generator to the load. The reactive part just bounces energy between the load and the generator, loading the network but not contributing to useful energy transfer. The harmonic part can occasionally transfer some power for some loads, but the network cannot deal efficiently with harmonic power transfer and for rotating machines and transformers it is damaging. Reactive power can be compensated with capacitors and harmonic power with passive or active filters.

Unbalance

Getting the 3-phase system powers is often more complicated than just adding the results for the individual phases. The graph in Fig. 3 shows the powers P, Q and S of a 3-phase system which is unbalanced. It demonstrates how we obtain the wrong answer if we calculate the apparent power S for a 3-phase unbalanced system by simply adding the individual phase results for S. We call this the arithmetic sum.

Fig. 3: A graphical display of an unbalanced 3-phase system.

Though we may always add the active powers P and the reactive powers Q, adding the apparent powers S is only valid if the system is perfectly balanced and contains no harmonics. If this is not the case, calculating an accurate value for the 3-phase system apparent power S is not so trivial. Although from this simplified graph it looks that the vector sum is the correct answer for S, it will turn out that even this is a too simplistic view. The unbalance causes unbalance power, which increases the value of S.

Symmetrical sequences

If we want to study the effect of unbalance in a 3-phase system, we’ll need a mathematical tool. The symmetrical sequences theory from CL Fortescue in 1918 is such a tool. In short it states that you can build any unsymmetrical 3-phase system from three symmetrical systems: One positive sequence system with the order A, B, C, one negative sequence system with the order A, C, B, and one zero sequence system in which A, B and C all point in the same direction.

Fig. 4: Symmetrical sequence theory.

Fig. 4 gives a graphical demonstration of this. Note that the positive and negative sequence systems are symmetrical. The zero sequence is a sort of common single-phase system. The positive sequence is the only one transporting useful power. It makes a motor run. The negative sequence acts as a break for a motor and the zero sequence just produces heat. The negative and the zero-sequence added together result in unbalance power. It is this unbalance power that increases the apparent system power in case of unbalance. Thus, unbalance in a 3-phase system means wasting energy.

Classical-IEEE-UPM

How unbalance power S1U influences the apparent power S is illustrated in this example. Three, 1200 W spotlights are connected to a 3-phase system. In the balanced situation this means 3600 W active power and 3600 VA apparent power. There is no phase shift, so no reactive power Q. Now one of the spotlights burns out completely. The remaining active power P is 2400 W, but the resulting apparent power S depends on the applied calculation method.

Fig. 5: Comparison of the Classical, IEEE and UPM calculation methods.

The classical method ignores unbalance all together. This is obviously wrong as there must be unbalance power involved. The IEEE method comes to the surprising conclusion that the apparent power S does not change due to a large unbalance power S1U. The unified power measurement (UPM) method leads to more moderate values for apparent and unbalance power. Which of the two is better? Hard to say. The academic debate about the definition of apparent power under extreme conditions is still going on. Fortunately, the numbers of the competing theories are closer together as the conditions are less extreme.

Power

Fig. 6 shows how the full powers can be broken down into smaller components each with particular characteristics. This process makes analysing power problems possible. The power components fit inside each other like a set of Russian Matryoshka dolls. Starting with the full powers, we first split off the fundamental components. The remainder forms the non-fundamental components, including harmonics.

Fig. 6: Deconstruction of power into smaller components.

The fundamental components can be further broken down into a positive sequence and unbalance parts. The unbalance part contains the negative and zero sequence components. By performing this power deconstruction, we can analyse the individual effects of unbalance and harmonics on a power system. The other way around it enables us to take efficient counter measures in case of “bad” power.

Utility to customer

The utility part of the network is separated from the customer part of the network by the metering point. This is where the amount of energy delivered is measured and billed to the customer. Not all energy paid for is efficiently used. Currents flowing through the in-house wires with finite resistance cause I2R losses in the form of heat.

Fig. 7: Illustration of how loads and losses occur in both the utility’s and the customer’s networks.

These losses register at the metering point as delivered active power, but do not contribute to the power delivered to the load. The utility puts the money wasted in its part of the network in the energy tariff. To minimise all this waste, we need insight in how the currents in the wires are composed to take effective countermeasures.

Current

By splitting up the currents into components which can be attributed to individual phenomena, we can deal with each current component in the most efficient way. We can identify five major current components, each leading to some sort of loss. The effective current is the only one giving useful energy transport. Reactive, unbalance and distortion currents do not contribute to efficiently transferring energy to the load. Unbalance and distortion lead to neutral currents causing losses in the neutral conductor.

Now we have deconstructed the current we can deal with the unwanted components individually. Reactive currents can be decreased with capacitors at the load, unbalance currents with balancing the load or using active or reactive balancing circuits, and distortion currents with active or reactive filtering. If we decrease unbalance and distortion the neutral current will also decrease. Ideally, we only have the effective current Ia+ causing I2R losses. There is little we can do about that except using lower resistance lines.

Send your comments to energize@ee.co.za

 

LEAVE A REPLY

Please enter your comment!
Please enter your name here

Latest Articles

Local branch opened in Limpopo

Hytec South Africa, a member of the Bosch Rexroth South Africa Group, officially opened its new branch in Lephalale, Limpopo in January 2020. The...

LED lighting controlled by a solar inverter

IMEON Energy announces the release of the LED Smart Lighting application (app) which enables its inverters to interact with smart LED lights from the...

EU plans energy system of the future

Information from the European Commission  -   To become climate-neutral by 2050, Europe needs to transform its energy system, which accounts for 75% of the EU's...

Industry association appoints new board

The South African Photovoltaic Industry Association (SAPVIA) appointed a new board at its recent Annual General Meeting (AGM). SAPVIA is an industry body which...

Popular fuel brand launches contactless fuel-payment app

Engen has announced the arrival of the new Engen 1app, which offers motorists a safe and conveniently contactless way to pay for fuel at its...

Covid-19 calls for “balanced” strategy for technical audits

Engineering projects face a growing range of audits, assessment and monitoring, but will Covid-19 restrictions on movement make it difficult for consultants to carry...

Alternator for cogeneration applications

Nidec Leroy-Somer announces the launch of the LSAH 44.3, an alternator designed for cogeneration applications in district heating. This new alternator incorporates an optimised...

Rapeseed natural ester fluid for EHV transformer

TransnetBW, a German electricity transmission operator, recently ordered a power transformer from Siemens. The specification called for the transformer to be filled with natural...

Natural gas to experience largest demand shock on record

Information from the International Energy Agency  -   Natural gas is expected to experience its largest demand shock on record in 2020 as the Covid-19 pandemic...

Coal for primary energy on the wane

Quoting the Yomiuri daily newspaper, Reuters reports that Japan is planning to suspend or close as many as 100 ageing and inefficient coal-fired power...

Hitachi ABB Power Grids commences operations

Complementary portfolios and technology strengths to ensure continuity, enhance customer value and bring growth opportunities. In accordance with the agreement signed on 17 December...

Energy efficiency: Still the low-hanging fruit

by Fereidoon P. Sioshansi, Ph.D, Menlo Energy -  Efficient use of energy is the key to a low carbon future. “In the battle against climate...

Wind and hydrogen offer potential to drive exports market

Information from the South African Wind Energy Association (SAWEA) The opportunity for South Africa to couple its renewable energy economic stimulus to non-electricity prospects, presents...

Carbon tax regulations regarding allowances and premiums

by Paula-Ann Novotny and Gillian Niven, Webber Wentzel On 19 June 2020, Tito Mboweni, the minister of finance, finalised the next set of regulatory mechanisms...

Battery packs for mobility and back-up power

In addition to supplying lithium iron phosphate (LiFePO4) battery packs for forklifts in materials-handling applications, Chase Technologies is also ramping up supply to ancillary...
- Advertisement -