-

Energize Maintaining backup battery systems for maximum usage and reliability
- Advertisment -

Maintaining backup battery systems for maximum usage and reliability

- Advertisment -

Information from Fluke  –  

Most backup power systems use an uninterruptable power supply (UPS) and a string of batteries. The UPS backs up the digital control system (DCS) to keep control of plant operations until systems can be safely shut down or until the auxiliary generator kicks on.

Although most batteries used in modern day UPS systems are “maintenance free”, they are still susceptible to deterioration from corrosion, internal shorts, sulphation, dry-out, and seal failure. This article outlines best practices for keeping these “battery banks” at optimum performance, so that if an outage does occur, the backup is ready.

Top two indicators of battery health

Internal battery resistance

Internal resistance is a life-span test, not a capacity test. Battery resistance stays relatively flat up until end-of-life draws near. At that point, internal resistance increases and battery capacity decreases. Measuring and tracking this value helps identify when a battery needs replacing.

Only use a specialised battery tester designed to measure battery resistance while the battery is in service. Read the voltage drop on the load current (conductance) or the AC impedance. Both results will be in ohmic values.

A single ohmic measurement is of little value without context. Best practice requires measuring ohmic values over months and years, each time comparing them to previous values on record to create a base line.

Discharge testing

Discharge testing is the ultimate way to discover the true available capacity of a battery but can be complicated to perform. In discharge testing, a battery is connected to a load and discharged over a specified period. During this test period, current is regulated, and a constant known current is drawn while voltage is measured periodically. Details of the discharge current, the specified time period for discharge testing, and the capacity of the battery in ampere hours can be calculated and compared to the manufacturers’ specification. For example, a 12 V 100 Ah battery may require a discharge current of 12 A for an eight-hour period. A 12 V battery would be discharged when the terminal voltage is 10,5V.

Batteries cannot support critical loads during and immediately after a discharge test. Transfer critical loads to a different battery bank until well after the test is complete and then reconnect a temporary comparably sized load to the batteries under test. In addition, before conducting the test, prepare a cooling system to compensate for a rise in ambient temperature. When large batteries discharge, they release a significant amount of energy expended as heat.

Healthy batteries should maintain a capacity above 90% of the manufacturer’s rating; most manufacturers recommend replacing the battery if it falls below 80%. When conducting battery tests, look for these indicators of failure:

  • Drop in capacity of more than 10% compared to the baseline or previous measurement
  • 20% or more increase in impedance compared to baseline or previous
  • Sustained high temperatures, compared to baseline and manufacturer’s specs
  • Degradation in plate condition

How to conduct standard battery tests

  • Float voltage: Isolate the battery or batteries from the charging system and the load. Measure the individual cell voltage or string using a digital multimeter or battery analyser such as monthly.
  • Charger output: Measure the charger output voltage at the charger output terminals using a digital multimeter or battery analyser such as the Fluke 500 Series Battery Analyser on a monthly basis. Observe the output current shown on the charger current meter or use an appropriate dc current clamp meter. Measure monthly.
  • DC float current: Refer to manufacturer’s specifications for approximate values for expected float currents. Use an appropriate dc current clamp meter to measure expected float current monthly.
  • Internal ohmic values: Use a battery analyser such as the Fluke 500 Series to measure the individual battery ohmic values every quarter. Establish reference values and maintain in the battery database.

Click here to watch a short demo video  

Contact Comtest, Tel 010 595-1821, sales@comtest.co.za

 

 

 

LEAVE A REPLY

Please enter your comment!
Please enter your name here

Latest Articles

Independent transmission system “essential” to end load shedding

by Roger Lilley, Now Media  -   To overcome the scourge of load shedding, two components are urgently needed: more generating capacity and an improved and...

Drivers improving the business case for solar power

Information from IM Power  -   Covid-19 has presented businesses with the opportunity to re-evaluate both their operational models and costs. Proactive organisations found themselves navigating...

Temperature monitor and controller saves municipality money

Instrotech recently supplied its DPM4003 and DPM3001M (low- and high-alarm relay output) temperature indicators to Levivi22 Engineering and Projects, the company contracted by Tshwane...

Undertaking wall thickness testing at Tutuka

During the lockdown in June, rope-access specialist Skyriders undertook an inspection of pulverised fuel (PF) piping at Tutuka power station near Standerton in Mpumalanga...

Rentable solar power now available

Aggreko, a leading provider of mobile, modular power, temperature control and energy services, today announces the immediate availability of its solar power rental offer....

EU solar power association signs cooperation agreement with SAPVIA

SolarPower Europe and the South African Photovoltaic Industry Association (SAPVIA) have signed a Memorandum of Understanding (MoU) to strengthen cooperation and explore new business...

First BW4 wind farm celebrates commencement of commercial operations

South Africa’s first bid window four (BW4) wind farm, part of government’s Renewable Energy Independent Power Producer Procurement Programme (REIPPPP), has announced its Commercial...

Maintaining backup battery systems for maximum usage and reliability

Information from Fluke  -   Most backup power systems use an uninterruptable power supply (UPS) and a string of batteries. The UPS backs up the digital...

Renewable energy company offers bursaries for tertiary education

Globeleq, a leading independent power producer operating in Africa, is offering bursaries for tertiary education. The Globeleq Scholarship Fund aims to develop skills needed...

SA’s Risk Mitigation tender and what it means for energy storage, renewables and gas

by Andy Colthorpe, Energy-Storage news  -   South Africa’s Ministry of Mineral Resources and Energy is conducting a fairly unique procurement programme for 2 GW of...

Eskom acknowledges load shedding’s damage to the economy, promises improvement

Eskom's CEO, Andre de Ruyter, says the power utility understands that it has a critical role to play in enabling South Africa's economic recovery...

MEA Energy Week conference draws world-class lineup

Information from Siemens  -  Siemens Energy and partners are holding a major Middle East and Africa-focused virtual conference, entitled ‘Shaping the Energy of Tomorrow’, from...

How to classify outdoor circuit breakers

Information from Noja Power  -   Electrical engineering switchgear classification is a challenging topic. With the varied terminology for electrical equipment around the world, clarity on...

What’s on the energy storage market besides Li-ion batteries?

Information from IDTechEx  -   While Li-ion batteries are dominating the stationary energy storage sector, a growing number of companies are developing different technologies to be...

Electrical junction box offers ten entries

A rectangular-shaped junction box, which is both Ex e and IP68 certified, is now available from Pratley. Known as the Enviro Rectangular Junction Box,...
- Advertisement -